Product Short Description
Product Name: Schneider Electric Modicon Compact I/O 4-Channel Analog Input Module.
Product Overview: The AS-BADU-204 is a 4-channel analog input module designed for the Modicon Compact PLC system. It converts field analog signals (temperature, pressure, flow, etc.) into digital signals for PLC processing, featuring high precision, high reliability, and a wide operating temperature range.
Description
Technical Specifications:
-
Module Type: Analog Input Module
-
Channels: 4 independent channels
-
Input Signal Types: Configurable — ±500 mV (2-wire sensors), PT100 (4-wire RTD), 0–20 mA, 4–20 mA, 0–10 V, -10 V to +10 V
-
A/D Conversion: Dual-slope integrating ADC, 12-bit resolution
-
Accuracy: ±0.1% FS or higher
-
Isolation Voltage: 1500 Vrms (channel-to-channel, enhancing EMI immunity)
-
External Power Required: 24 VDC @ 250 mA (if not supplied, the module draws from the internal bus and produces erroneous readings)
-
Operating Temperature: 0 °C to 55 °C (some sources: -20 °C to +60 °C)
-
Relative Humidity: 5% to 95%
-
Protection Rating: IP20 or higher
-
Dimensions: 70 mm × 100 mm × 60 mm
-
Weight: approx. 0.2 kg
-
Mounting: DIN rail or Modicon Compact rack
-
Interface: Phoenix terminal connection, supports shielded twisted-pair wiring (e.g., Belden 9418)
Key Features:
-
Dual-slope integrating A/D conversion for accurate data acquisition
-
Per-channel independent configuration for flexible signal type selection
-
Channel-to-channel isolation for strong anti-interference capability
-
LED indicators: green LED for module ready/data transmission; red LED for open current loop or high loop impedance (>500 Ω) detection
-
Supports Modbus RTU/ASCII communication protocols
Application Scenarios:
-
Process control: monitoring and control of temperature, pressure, flow parameters
-
Petrochemical: monitoring and controlling various process parameters
-
Power: monitoring and control of power systems
-
Metallurgy: process control in the metallurgical industry
-
Building automation and manufacturing production line control
Installation & Usage Notes:
-
Requires external 24 VDC power (250 mA); failure to provide this results in erroneous readings
-
Signal cables must use shielded twisted-pair wiring, grounded only at the module end to avoid crosstalk
-
Route signal cables away from motors, transformers, and other strong EMI sources; cross布线 at right angles when crossing
-
DIN rail mountable for convenient control cabinet installation