Product Short Description
Product Name: AutomationX aXlink100, Ethernet-PROFIBUS Gateway/Connector Module
Product Introduction: The aXlink100 is a real-time gateway device developed by AutomationX (part of GAW Group) that connects Ethernet and PROFIBUS networks using Xlink, AutomationX’s proprietary real-time Ethernet protocol. It is designed for AutomationX software version 4.7 and higher, enabling seamless integration of PROFIBUS-DP slaves into Ethernet-based automation architectures.
Description
Technical Specifications:
-
Order Number: aXlink100
-
CPU: netX (200 MHz ARM9)
-
RAM: 8 MB
-
System Memory: Micro-SD card
-
Ethernet Interfaces: 2 × 100 Mbit/s (RJ45 connector)
-
PROFIBUS Interface: 1 × PROFIBUS-DP Master (9-pin Sub-D female connector)
-
Baud Rate: Up to 12 MBaud
-
Supply Voltage: 14–30 V DC (redundant 24 V DC supported)
-
Current Consumption: 0.15 A average
-
Power Consumption: 8.2 W
-
Dimensions: 105 × 45 × 118 mm
-
Protection Type: IP20
-
Max PROFIBUS Masters per system: 16 (aXlink100 units)
-
Max PROFIBUS-DP Slaves per gateway: 124
Functional Features:
-
Real-time protocol conversion using Xlink
-
High bandwidth data transfer
-
Redundancy support with bumpless redundant switching
-
Support for various network topologies: line, ring, tree, redundant tree
-
Ring topology without expensive fiber optic cabling
-
No configuration required for address switching
-
Diagnostic via LED indicators and protocol
-
DIN rail mounting
Application Scenarios: Process automation, industrial Ethernet infrastructure, PROFIBUS peripheral integration, redundant network architectures, and migration projects where legacy PROFIBUS devices must connect to modern Ethernet-based control systems.
Operating Principle: Uses the Xlink real-time Ethernet protocol to bridge PROFIBUS-DP and Ethernet. With two Ethernet interfaces, an electric ring can be configured via CAT5 cables, or network/server redundancy can be implemented in star-shaped networks with switches. Each unit can connect up to 124 PROFIBUS-DP slaves to the AutomationX system.
Installation Requirements: DIN rail mounting inside control cabinet. Provide stable 14–30 V DC power (redundant 24 V DC recommended). Use shielded twisted-pair Ethernet cable (Cat5e or better). Properly terminate and bias PROFIBUS-DP segments. Connect both Ethernet interfaces for ring or redundant topologies.
Environmental Specifications:
-
Operating Temperature: -10 °C to 70 °C
-
Storage Temperature: -20 °C to 80 °C
-
Relative Humidity: < 90% (non-condensing)
Usage Precautions: After power-up, monitor LEDs for green “link up” status on Ethernet ports and PROFIBUS master interface. In redundant setups, the module supports automatic switchover on link failure. In redundant configurations, hot-swapping a failed unit is possible without disrupting the entire network. Firmware/configuration accessed via AutomationX engineering tools.