The TRICONEX 4351B is a triple modular redundant (TMR) safety communication module designed exclusively for Tricon V10.0 and higher TMR Safety Instrumented Systems. It serves as the unified communication gateway between the Tricon controller and external systems including DCS, operator stations, historians, and third-party field devices, handling all protocol conversion and message buffering independently from the main safety processor.

Description

Technical Specifications:
  • Model:​ 4351B
  • Manufacturer:​ TRICONEX (Schneider Electric)
  • Product Type:​ TCM Triple Redundant Safety Communication Module
  • Compatible System:​ Tricon V10.0 and above TMR SIS
  • Serial Interfaces:​ 4 × RS-232/RS-422/RS-485 universal serial ports (DB9)
  • Ethernet Interfaces:​ 2 × 10/100M adaptive RJ45 ports (fiber optional)
  • Serial Speed:​ Up to 115.2 Kbps per port; aggregate 460.8 Kbps across four ports
  • Supported Protocols:​ Modbus RTU/TCP, TriStation, TSAA, SNTP, UDP/IP, Trimble GPS
  • Port Isolation Voltage:​ 500 VDC channel-to-channel electrical isolation
  • Internal Memory:​ 1 MB RAM, 4 MB Flash program storage
  • Communication Processor:​ Dedicated 32-bit communication CPU
  • Safety Certification:​ IEC 61508 SIL 3, TÜV certified
  • Power Input:​ 24 VDC ±10%
  • Power Consumption:​ ≤5 W
  • Operating Temperature:​ -40 °C to +70 °C
  • Physical Dimensions:​ 275 mm × 128 mm × 36 mm
  • Weight:​ 3.18 kg
  • Mounting:​ Tricon standard rack, hot-swappable, error-proof keying
  • Protection Rating:​ IP20 (control cabinet installation)
Functional Features:
  • Dedicated 32-bit communication processor offloads all protocol conversion from the main safety CPU, ensuring ESD and F&G logic scan times are never affected by communication load
  • Four independent electrically isolated serial ports allow simultaneous polling of multiple protection relays, vibration monitors, and PLCs
  • Dual Ethernet ports support Modbus TCP, SNTP, TSAA multicast, OPC, and TriStation host communication for DCS integration, historian upload, and peer-to-peer Tricon controller linking
  • Port 1 dedicated for Modbus and Trimble GPS clock synchronization; Port 4 for TriStation local engineering downloads
  • Built-in 1 MB RAM and 4 MB Flash for message buffering and firmware storage
  • Front panel indicators: PWR (backplane power), OK (TMR voting healthy), FAULT (communication/hardware fault), ETH1/ETH2 (Ethernet activity), PORT1–PORT4 (serial activity)
  • Hot-swappable with anti-misinsertion mechanical keying
  • 500 VDC port-to-port isolation prevents a single external link fault from disturbing other channels or the safety computation
Application Scenarios:
  • Petrochemical and oil refinery ESD/F&G system communication gateways
  • Offshore oil platform safety instrumented system networking
  • Thermal power plant turbine protection system data exchange
  • Integration of Tricon SIS with DCS, SIS historian servers, and operator workstations
  • Cross-system interlock signal exchange between multiple Tricon controllers
  • GPS time synchronization for event sequence recording across safety systems
  • Any SIL 3 safety application requiring high-bandwidth, multi-protocol external communication
Installation Requirements:
  • Install in a Tricon V10.0 or higher main chassis with proper backplane engagement
  • Verify 24 VDC ±10% power supply with adequate current capacity
  • Configure serial port mode (RS-232/422/485) via baseplate wiring per port requirement
  • Connect Ethernet ports to the appropriate network segments with correct IP addressing
  • Ensure control cabinet ambient temperature remains within -40 °C to +70 °C
  • Properly ground the rack to leverage 500 VDC port isolation benefits
  • Use TriStation 1131 for module configuration and firmware management
Usage Notes:
  • The module’s dedicated 32-bit CPU means communication traffic will never impact the safety logic scan cycle
  • Serial ports are independently isolated — a fault on Port 1 cannot propagate to Port 2, 3, or 4
  • Only install in Tricon V10.0 or higher systems — earlier versions are not supported
  • The FT FAULT LED indicates communication, hardware, or backplane faults and should be investigated immediately
  • Replacement modules must run firmware compatible with the host Tricon system version
  • GPS time synchronization via Port 1 requires a Trimble-compatible GPS receiver