Product Short Description

Product Name: Analogue Output Termination Assembly (AOTA)

Product Brief: Simplex termination assembly for analogue output modules, used to connect controller analogue output modules and field modulating actuators, dedicated for Regent & Trusted TMR safety control systems.

Technical Specifications:

  • Channel Quantity: 8 analogue output channels, simplex configuration

Description

  • Supported Signal: 4–20mA current signal, 0–10V voltage signal
  • Isolation Rating: 1500V DC channel isolation
  • Operating Voltage: 24V DC nominal (18V–32V DC)
  • Resolution: 12-bit
  • Accuracy: ±0.2% full scale
  • Power Consumption: Max 1W
  • Operating Temperature: -20°C ~ +60°C
  • Humidity: 5% ~ 95% RH, non-condensing
  • Enclosure Protection: IP20
  • Dimensions: 132mm × 42mm × 35mm
  • Weight: 130g

    Function Features:

  • Continuous self-diagnosis for internal circuit and field loop fault detection
  • Support single simplex channel configuration for safety instrumented systems
  • Integrated terminal wiring base, direct pluggable connection with main I/O module
  • Overload protection for each signal channel

    Working Principle: Convert internal bus analogue control signals to standard field analogue signals, provide wiring interface, detect open circuit and short-circuit faults of field cables, and feed fault information back to the main controller.

    Material Composition: FR4 printed circuit board, flame-retardant ABS plastic housing, copper alloy terminal connectors, industrial-grade surface-mount electronic components.

    Structural Characteristics: Plug-in card structure, matched system rack slot installation; upper terminal wiring area, lower backplane connector; modular split design convenient for maintenance without rewiring.

    Application Scenarios: Oil & gas process control, petrochemical SIS safety system, power plant boiler control, refining unit modulating valve control.

    Installation Requirements: Install in standard control cabinet rack, vertical mounting; maintain 20mm ventilation gap between adjacent modules; wiring conductor maximum cross-section 1.31mm² (16AWG), wire stripping length 6mm.

    Usage Notes: Strictly avoid signal wiring and power cable parallel laying; do not hot plug under load; regularly check terminal fastening torque; conformal coated version applicable for high-corrosion environments.