Product Short Description

Product Brief Introduction

Dry contact type digital input terminal assembly without external field voltage requirement; detects passive mechanical switch contact closure signals from field instruments, fully isolated design for low-voltage discrete signal acquisition.

Description

Technical Specifications

  1. Channel Quantity: 8 isolated dry contact input channels
  2. Internal Sensing Circuit: 24 VDC low-current sense voltage supplied by DCS internal circuit
  3. Contact Detection: Identifies open / closed passive mechanical contacts (limit switches, proximity relays, door interlocks)
  4. Channel Isolation: 1500 VAC isolation per channel
  5. Diagnostic Function: Open wire fault detection for each field wiring loop

Structural Characteristics

Integrated wire strain relief brackets, transparent terminal safety cover, front panel per-channel status LED indicators, anti-mismatch mechanical coding key.

Working Principle

Internal 24VDC low-power sensing circuit applies weak voltage across field dry contact terminals; when mechanical contact closes, current loop forms, optocoupler converts conduction state to digital input logic signal for DeltaV controller processing.

Typical Applications

  • Valve limit switches, equipment safety interlock doors, low-voltage proximity sensors, cabinet thermal alarm switches
  • Food & beverage, pharmaceutical, water treatment low-voltage discrete control systems

Operation Precautions

  • Do not connect external AC/DC power sources to dry contact terminals; external voltage will burn internal sensing circuits
  • Keep field contact wiring length under 100 meters to avoid leakage current false triggering