Product Short Description
Product Brief Introduction
8-channel AC digital input terminal block designed for 120VAC field contact signal collection, full channel galvanic isolation to filter industrial motor and contactor electromagnetic noise, dedicated for high-voltage discrete field status feedback signals in DeltaV DCS system.
Description
Core Technical Parameters
- Channel Count: 8 independent digital input channels
- Rated Field Input Voltage: 120 VAC 50/60 Hz
- Isolation Voltage: 2000 VAC between field circuit and control backplane
- Input Trigger Threshold: Logic ON ≥ 90 VAC; Logic OFF ≤ 20 VAC
- Per-channel LED status indicator for real-time contact state visualization
- Wiring Terminal: Cage clamp screw terminals for stranded copper field wiring
Structure & Material
Black flame-retardant ABS plastic housing, built-in surge absorption TVS diodes on each input channel, mechanical anti-mismatch coding key.
Working Principle
120VAC field switch contact signals pass through current-limiting resistors and surge suppression components, then optocoupler isolation circuits convert AC voltage signals to digital logic levels readable by DeltaV DI function cards. Isolation barrier eliminates ground loop interference from high-voltage field equipment.
Application Scenarios
- Motor running status feedback, high-voltage valve position limit switches, cabinet AC fault alarm contacts
- Refinery, power plant, heavy industry discrete equipment status monitoring
Installation & Usage Rules
- Only compatible with matching KJ3001 series 120VAC DI function cards; key lock blocks incorrect module pairing
- Field AC wiring must separate from low-voltage analog signal cables with minimum 15cm distance