Product Short Description
Product Overview
High-sensitivity ultraviolet flame detection unit designed for industrial burners, boilers, incinerators. Captures UV spectral radiation generated by fuel combustion, outputs switch signal to combustion safety interlock system to prevent fuel leakage explosion risk caused by flame loss.
Description
Technical Specifications
- Detection spectrum: 180 nm ~ 260 nm UV-C band
- Rated operating voltage: 24 V DC ±10%
- Power consumption: Max 6 W
- Flame response time: <200 ms
- Relay output contact capacity: 5 A @ 250 V AC NO/NC dual contacts
- Ambient operating temperature: -20°C ~ +70°C; up to +150°C with cooling air purge
- Protection class: IP66
- Cable interface: M20 waterproof threaded connector
- Dimensions: 145 mm × 68 mm × 52 mm
- Net weight: 0.42 kg
Function Features
- Anti-interference optical filter design, eliminates sunlight, incandescent lamp, electric arc false flame detection
- Built-in automatic self-test circuit, periodic self-check of UV sensor failure, circuit open/short circuit
- Adjustable flame sensitivity threshold via potentiometer on front panel, adaptable to natural gas, diesel, coal powder, hydrogen fuel
- Dual channel fault signal output: local LED indicator light + remote relay alarm contact
- Reverse power connection protection, overvoltage surge protection built-in circuit
- Long service life UV photoelectric tube, no frequent replacement
- Compliant with international combustion safety certification standards
Application Scenarios
Marine boiler combustion safety monitoring, thermal power plant auxiliary burner flame detection, industrial gas boiler, waste incinerator, heating furnace, petrochemical heating furnace, hydrogen fuel burner, metallurgical smelting furnace interlock protection system.
Performance Parameters
- UV detection distance maximum: 12 m under clean combustion environment
- Flame loss interlock delay: adjustable 0.5 s ~ 10 s
- Vibration withstand: 5–200 Hz, 2 g continuous vibration without malfunction
- Service life of UV sensor tube: ≥50,000 working hours
- Cold storage temperature: -40°C ~ +75°C
- Insulation resistance between power terminals: ≥100 MΩ
Material Composition
- Outer housing: Die-cast aluminum alloy with hard anodized anti-corrosion surface
- Optical window: High-transmittance UV quartz glass, anti-scratch coating
- Internal circuit board: FR4 anti-high temperature PCB, tin-plated copper traces
- Sealing ring: EPDM ethylene propylene rubber waterproof gasket
- Internal sensor core: Vacuum UV photoelectric tube with nickel alloy electrode
Structural Characteristics
Cylindrical compact integrated structure, front optical detection window, rear wiring terminal cavity separated by isolation baffle to avoid high temperature heat transfer to circuit board. Built-in axial air cooling channel for high-temperature furnace wall installation. Rotatable mounting flange with 360° angle adjustment for aligning flame viewing angle. Independent terminal wiring compartment with waterproof compression cable gland.
Working Principle
Combustion flame releases characteristic ultraviolet radiation within 180–260 nm wavelength; UV light penetrates quartz window and irradiates vacuum UV photoelectric tube inside the module, triggering photoelectric emission effect to generate micro current signal. Internal signal amplifier amplifies weak current, comparator circuit judges whether flame intensity exceeds preset threshold. If flame exists, relay keeps closed; once flame disappears, signal current drops below threshold within 200 ms, relay cuts off contact and outputs flame failure alarm signal to trigger burner fuel valve interlock cut-off.
Installation Requirements
- Install at 15°–75° inclination angle aiming at stable flame core area, avoid direct alignment with furnace wall high-temperature reflection surface
- Reserve compressed air purge pipeline interface to blow soot and dust on quartz window regularly
- Wiring cable uses shielded wire, shield layer single-point grounding at control cabinet end
- Mount cooling air pipe if installation surface temperature exceeds 70°C; cooling air pressure 0.2–0.4 MPa dry clean compressed air
- Fix mounting flange with stainless steel bolts, add high-temperature resistant graphite gasket between flange and furnace wall
- Keep minimum 200 mm distance from ignition transformer to avoid electromagnetic interference
Use & Maintenance Precautions
- Clean quartz optical window every 3 working days to remove soot accumulation which will reduce detection sensitivity
- Do not use corrosive solvent to wipe quartz glass; only soft microfiber cloth with anhydrous ethanol
- Avoid mechanical impact on front optical window, quartz glass crack will completely lose detection function
- Check air purge pipeline unobstructed daily; blocked air pipe leads to window fouling and false flame loss alarm
- Replace UV photoelectric tube every 50,000 working hours to guarantee detection accuracy
- Disconnect 24V DC power before disassembling module; do not touch internal circuit components with bare hands
- Regular test flame loss interlock function by cutting off fuel supply manually to verify alarm output validity