Product Short Description
Product Brief Introduction
High-current variant of TDK-Lambda RM-GB 15 V output industrial switching power supply, fixed 15 V DC 4 A rated output 60 W total power, universal wide AC input range, optimized for high-current industrial control load equipment. Retains full series protection circuit and long-life component design for heavy-duty continuous automation cabinet power supply application.
Description
Core Technical Performance Parameters
Input Specifications
- Input Voltage Range: 85–132 V AC single phase
- Input Frequency: 47–440 Hz wide industrial frequency range
- Max Input Apparent Power: 110 VA at full 4 A output load
- Internal Input Fuse: 3.15 A slow blow safety fuse
- Cold Start Inrush Current: Max 17 A peak at 25 °C ambient
- Max Leakage Current: 0.5 mA maximum
Output Specifications
- Nominal Output Voltage: 15 V DC
- Rated Continuous Output Current: 4.0 A
- Full Rated Output Power: 60 W
- Output Voltage Adjustment Range: ±10% via front panel trim potentiometer
- Output Ripple Noise: ≤50 mV peak-to-peak 20 MHz bandwidth measurement
- Line Regulation: ≤0.5% full input voltage swing
- Load Regulation: ≤0.5% 0–100% load variation
- No-load Operation Support: Stable output under zero output current condition
Protection & Environmental
- Integrated Protection Circuits: Overvoltage protection (120–150% Vout threshold), constant current overload limiting, auto-recovery short-circuit shutdown, input reverse polarity protection
- Typical Full Load Efficiency: 76% at 110 V AC input
- Continuous Operating Temperature: 0 °C to +50 °C full rated power; linear power derating above 50 °C
- Storage Temperature Range: -20 °C to +85 °C
- Input-Output Isolation: 4300 V DC reinforced safety isolation
- Safety Certifications: UL, CSA, CE, IEC 60950-1 industrial control equipment standard
- Net Weight: 0.38 kg
Function & Feature Highlights
- High 4 A continuous output current capacity to power multiple parallel low-power control modules simultaneously
- Wide 47–440 Hz input frequency compatibility for marine, generator-powered off-grid industrial power grid
- Automatic recovery short-circuit protection, no manual power cycle required after fault removal
- Reinforced 4.3 kV isolation meets IEC safety separation standard for cabinet control and power circuit isolation
- Low leakage current design, suitable for marine automation and medical low-interference equipment power supply
- Multi-stage EMI input filter suppresses industrial grid voltage spikes and high-frequency harmonic noise
- High-temperature rated long-life electrolytic capacitors extend service life under continuous full-load operation
- Front panel adjustable output voltage potentiometer for precise matching of sensitive sensor and amplifier load equipment
Working Principle
- Single-phase AC mains input flows through multi-stage EMI filter to eliminate grid high-frequency interference, then rectified into high voltage DC bus voltage.
- PWM high-frequency switching circuit and isolation ferrite transformer execute voltage step-down conversion to secondary low voltage high-current pulse signal.
- Secondary synchronous rectifier and LC low-pass filter convert high-frequency pulse waveform into stable low-ripple 15 V DC high-current output.
- Output voltage sampling feedback loop dynamically adjusts PWM switching duty cycle to maintain constant output voltage during input voltage fluctuation and load current variation.
- Independent hardware protection circuit monitors output voltage, output current and input polarity; immediately cuts PWM switching drive signal to protect internal power components once fault condition detected.
Material & Structural Composition
- Outer Enclosure: Galvanized cold rolled steel sheet with anti-rust black coating, ventilation slot design for passive cooling
- Main Circuit PCB: High TG FR4 fiberglass substrate, lead-free solder plating
- Power Core Components: Low Rds(on) high-efficiency MOSFET switching tubes, large capacity high-frequency ferrite transformer
- Energy Storage Capacitors: 105 °C rated long-life aluminum electrolytic capacitors
- EMI Filter Assembly: Common mode and differential mode dual-stage filter inductors
- Adjustment Component: Precision carbon film trimming potentiometer for output voltage fine tuning
- Terminal Connectors: Large capacity tin-plated copper screw terminals for high-current output wiring
Installation Requirements
- Vertical cabinet mounting orientation mandatory, minimum 25 mm vertical clearance above and below unit for natural convection heat dissipation
- Avoid installation adjacent to high heat generating equipment (servo drives, brake resistors, power transformers)
- Input AC wiring minimum cross-section 1.25 mm² copper wire; output high-current wiring use minimum 1.5 mm² copper cable to reduce voltage drop
- Protective earth ground terminal must be reliably connected to cabinet metal ground rail for safety isolation
- Separate input AC wiring and output DC wiring routing to avoid electromagnetic cross interference
Application Scenarios
- Multi-module PLC/DCS control cabinet centralized auxiliary power supply
- Marine vessel distributed I/O module high-current power source
- Hydraulic proportional valve amplifier bank centralized power supply
- Automated production line sensor array and signal converter power supply
- Industrial robot peripheral auxiliary control circuit power supply
Operation & Maintenance Precautions
- Ambient temperature above 50 °C requires linear output current derating, continuous full load operation at high temperature will shorten capacitor service life
- Avoid continuous short-circuit operation over 10 seconds; repeated long short-circuit cycles degrade internal switching tube performance
- Input AC voltage must not exceed maximum 132 V AC rating, overvoltage will blow internal input safety fuse
- Do not cover housing ventilation slots with cables, cable ties or cabinet accessories; blocked airflow causes overheating thermal shutdown
- Conduct semi-annual ventilation slot dust cleaning to maintain optimal heat dissipation efficiency






Reviews