Product Short Description
Product Brief Introduction
This is an explosion-proof intelligent fire alarm and extinguishing system controller produced by MINIMAX fire protection brand, certified for hazardous explosive zone environments, integrated smoke/temperature fire signal collection, extinguishing agent release logic control, fault self-diagnosis and remote communication functions, dedicated to oil & gas, chemical plant, offshore platform Class I/II explosive dangerous area fire safety monitoring and automatic fire suppression control.
Description
Core Technical Specifications
- Input Power Supply: AC 110/230V dual-range switching power supply, backup 24VDC built-in lithium battery (72h standby)
- Signal Input Channels: 16 analog fire detector input channels (4–20mA smoke/temperature sensor)
- Output Control Channels: 8 relay output channels for extinguishing solenoid valve, alarm horn, fire damper interlock
- Explosion Protection Standard: Ex d IIC T6 Gb, IP66 full enclosure waterproof dustproof grade
- Communication Interface: RS485 Modbus RTU, fire system dedicated bus for upper fire host connection
- Operating Temperature: -40°C ~ +70°C
- Relative Humidity: 5%–95% non-condensing
- Certifications: ATEX, IECEx, UL fire safety, SIL2 functional safety certification
- Cabinet Dimensions: 420mm × 310mm × 165mm, total weight 6.8kg
- Extinguishing Delay Adjustable Range: 0–300 seconds programmable
Functional Features
- Full explosion-proof cast aluminum enclosure design, safe deployment in Zone 1, Zone 2 explosive gas hazardous areas
- Independent channel fire signal threshold configuration, separate smoke and temperature dual-judgment fire logic to avoid false alarm
- Complete circuit fault diagnosis: detector open circuit, short circuit, power loss, solenoid valve wiring break real-time monitoring
- Programmable multi-stage interlock logic: fire detection → audible/visual alarm → adjustable delay → automatic extinguishing agent release
- Built-in historical event storage, record fire alarm, fault, extinguishing action logs for 5 years retrievable
- Remote monitoring via Modbus communication, real-time upload fire status to central fire control room
- Manual emergency release button interface for on-site manual trigger fire suppression under emergency situation
- Anti-interference EMC circuit design, stable operation under strong electromagnetic interference of chemical plant frequency conversion equipment
Working Principle
- Smoke and temperature fire detectors transmit 4–20mA analog fire intensity signal to each input channel of WMX1000F90 control panel.
- Main control chip compares real-time detector signal with preset alarm threshold; when single/double channel signal exceeds threshold, enter pre-alarm state and activate local audible-visual alarm output.
- If fire signal persists beyond confirmation delay time, control panel triggers extinguishing output relay to open fire suppression agent storage tank solenoid valve, release foam/gas fire extinguishing medium.
- Diagnosis circuit scans all input/output wiring every 100ms; abnormal circuit state stored as fault code and uploaded to upper monitoring system via RS485 bus.
- Built-in backup lithium battery automatically switches power supply once AC mains power fails, maintain full system monitoring function for 72 hours continuously.
Structure & Material Composition
- Explosion-Proof Main Cabinet: High-pressure die-cast aluminum alloy thick wall shell, internal flame-proof separation cavity structure
- Cabinet Seal: EPDM rubber fully surrounding waterproof sealing gasket, anti-aging oil resistant
- Internal Circuit Board: FR4 fire-retardant PCB, all electronic components explosion intrinsically safe certified
- Terminal Chamber: Independent separated wiring explosion-proof cavity, external cable compression gland with IP66 waterproof
- Operation Interface: Explosion-proof transparent tempered glass observation window, internal LED status indicator, sealed non-spark operation buttons
Installation Requirements
- Mount on vertical wall of hazardous explosion zone, minimum 1.5m height from ground, avoid direct flushing of production process water
- All external signal and power cables must use explosion-proof metal armored cable, matched certified cable compression glands only
- Separate wiring for fire detector signal cable and high-power equipment power cable, routing distance ≥ 30cm to eliminate signal interference
- Cabinet grounding terminal connected to factory hazardous area dedicated safety ground network, ground resistance ≤ 0.5Ω
- Reserve 20cm maintenance space on all four sides of explosion-proof cabinet, do not block heat dissipation and wiring cavity
- Explosion-proof cabinet cover bolt tightening torque strictly follow factory standard 4.0 N·m evenly diagonal locking
Application Scenarios
Offshore oil & gas platforms, chemical raw material storage warehouses, petrochemical refining workshops, gas compressor stations, paint spraying hazardous workshops, pharmaceutical solvent production lines.
Operation & Maintenance Precautions
- Only factory-certified explosion-proof maintenance personnel allowed to open cabinet cover; power must be fully cut off before opening explosion-proof cavity
- Do not replace internal circuit components with non-SIL2 certified parts, will lose explosion-proof and fire safety certification validity
- Inspect cabinet EPDM sealing gasket every 6 months; replace gasket once aging cracking or deformation found
- Regular test backup lithium battery capacity annually; replace battery if standby time shorter than 48 hours
- Do not install this unit in environment with corrosive acid/alkaline gas; corrosive gas will damage aluminum explosion-proof shell
- Clean cabinet surface only with neutral water-based cleaning agent, prohibit organic solvent wiping transparent observation window






Reviews