Product Short Description
Basic Product Identity
- Manufacturer: ALSTOM (Asset transferred to GE Vernova Grid Solutions)
- Full Product Name: EP Series Three-Phase Undervoltage Protection Relay / ESP Electrostatic Precipitator Main Control Module
- Model Series: EP Series Protection & Control Module Platform
Description
Product Brief Introduction
Dual-purpose industrial static microprocessor module, core equipment for power grid undervoltage protection and flue gas electrostatic precipitator master control. Adopts full analog-digital hybrid circuit architecture, integrates fault detection, thyristor firing control, spark suppression and power system voltage monitoring functions, compliant with IEC 60255 power protection standards, designed for continuous long-term operation in high-dust, electromagnetic interference industrial environments.
Core Technical Specifications
- Rated Input Voltage: 100V AC / 110V AC three-phase line voltage (power protection version); 110/220V AC jumper-selectable (ESP control version)
- Rated Operating Frequency: 50 Hz fixed
- Power Consumption: < 30 W full-load operation
- Analog Input Channels: 4 channels 0–10V DC, 16-bit high resolution
- Control Output Signals: 4-channel 4–20mA analog output; thyristor SCR gate firing pulse output; rapper mechanical vibration control relay outputs
- Communication Interface: RS485 serial bus, Modbus RTU / Profibus compatible via gateway module
- Physical Dimensions: 340mm × 125mm × 68mm
- Net Weight: 1.20 kg
- Protection Grade: IP20 cabinet-mounted indoor grade
- Operating Ambient Temperature: -10°C ~ +60°C
- Storage Temperature: -30°C ~ +70°C
- Humidity Tolerance: 5%–90% RH non-condensing
Function Features
- Three-phase synchronous undervoltage fault detection with independent phase judgment logic, instantaneous trip signal output when line voltage drops below calibrated threshold
- ESP spark rate closed-loop regulation, intermittent energization algorithm to reduce power consumption while maintaining maximum fly ash capture efficiency
- Full real-time secondary voltage, secondary current and primary current sampling monitoring
- Built-in hardware watchdog circuit, automatic reset and fault lockout upon processor crash
- Multi-level user parameter password lock to prevent unauthorized modification of protection threshold values
- Continuous self-diagnosis of internal power circuit, input signal open/short circuit fault identification
Performance Parameters
- Undervoltage Action Delay Range: 0.1s ~ 99.9s continuously adjustable
- Measurement Accuracy Class: 0.5 for voltage/current sampling
- Maximum Spark Suppression Response Speed: < 10ms
- Isolation Withstand Voltage: 2000V AC between signal circuit and power circuit
- Overvoltage Withstand Capability: 1.5× rated input voltage continuous operation without damage
Material Composition
- Outer Housing: Cold-rolled steel sheet with anti-corrosion matte black electrostatic spraying
- Internal Circuit Board: FR4 high-temperature resistant flame retardant PCB, tin-lead free surface treatment
- Terminal Block: PA66 flame retardant plastic, copper alloy conductive terminals with nickel plating anti-oxidation coating
- Internal Capacitors: High-temperature electrolytic capacitors with 10,000-hour service life at 60°C
Structural Characteristics
- Standard 19-inch rack-mount modular plug-in structure, hot-swappable compatible with ALSTOM EP series backplane
- Front panel equipped with digital parameter display screen, physical setting buttons and fault LED indicator lights
- Rear side fixed screw terminal wiring layout, independent wiring area separated from main circuit board for anti-interference
- Internal segmented shielding compartment, independent shielding layers for power circuit and signal circuit
Working Principle
- Power Protection Mode: Three-phase line voltage signals pass through isolated voltage transformers, converted to DC sampling signals sent to main processor; processor compares real-time voltage with preset undervoltage threshold, triggers relay trip output when voltage is lower than setting value to cut off load equipment
- ESP Control Mode: Real-time acquisition of T/R transformer secondary electrical parameters, calculates spark frequency via embedded algorithm, outputs adjustable thyristor firing angle signals to control transformer output voltage; automatic power reduction during frequent sparking to avoid electrode breakdown, and outputs timing signals for ash removal rapper equipment
Advantage Highlights
- Unified hardware platform supports two major industrial application scenarios (power grid protection / flue gas emission control), reduces spare parts inventory cost
- Ultra-high anti-electromagnetic interference performance, stable operation under strong harmonic and arc interference environment
- Long service life industrial grade components, designed for 10-year continuous operation without regular component replacement
- Complete fault data storage function, retains 500 groups of historical fault records for post-failure analysis
- Modular plug-in design, single module replacement without system overall shutdown
Applicable Industries
Thermal power generation plants, waste incineration power stations, cement manufacturing factories, metallurgical smelting enterprises, medium-voltage power distribution substations, industrial flue gas treatment environmental protection systems
Installation Requirements
- Mount inside sealed industrial control cabinet, vertical installation angle deviation ≤ 15°, avoid direct air duct blowing on module surface
- Maintain ≥ 50mm heat dissipation gap above and below the module in the cabinet
- Separate power wiring and signal wiring into different wiring grooves, wiring distance ≥ 100mm
- Equip cabinet with temperature control fan when ambient temperature exceeds 45°C
- Connect cabinet grounding terminal to factory protective earth with 4mm² copper grounding wire
Usage Precautions
- Do not operate the module outside the specified voltage range, overvoltage will permanently damage internal sampling transformers
- All parameter modification operations must be recorded and backed up before adjustment
- Cut off all power supply before opening the module housing for inspection
- Do not use compressed air to blow dust inside the module, residual moisture will cause circuit short circuit
- If frequent fault alarms occur, inspect external voltage transformer wiring open circuit first before module maintenance

.jpg)