Product Short Description

Product Brief

Dedicated rack-mounted analog module for platinum resistance temperature sensor signal collection, supports PT100/PT1000 three-wire RTD sensors, applied for low-medium temperature industrial process monitoring, no L extended shielding variant.

Description

Technical Specifications

  • Model Series: ACN CS D2014 Special Analog Acquisition Subseries
  • Power Supply: 24 VDC ±10, rated power consumption 10.5 W
  • RTD Input Channels: 8 three-wire isolated RTD channels
  • Supported Sensor Types: PT100, PT1000 configurable per channel
  • Temperature Measurement Range: -200 °C ~ +850 °C
  • Signal Resolution: 16-bit high-precision ADC conversion
  • Backplane Bus: Metso proprietary ACN high-speed internal bus
  • Operating Temperature: -20 °C ~ +60 °C
  • Storage Temperature: -40 °C ~ +85 °C
  • Humidity Tolerance: 5%–95% non-condensing
  • Protection Grade: IP20 module body, IP54 full rack assembly
  • Dimension: 220 H × 160 W × 35 D mm
  • Net Weight: 0.74 kg

Functional Features

  1. 8 independent three-wire RTD acquisition channels with full isolation
  2. Automatic wire resistance compensation for three-wire RTD cable length deviation
  3. Per-channel RTD sensor open/short circuit fault self-diagnosis
  4. Front panel independent LED over-temperature alarm indicator for each channel
  5. Onboard Flash memory stores RTD linear calibration parameters
  6. Full hot-swap compatible with ACN CS rack backplane
  7. Automatic PT100/PT1000 sensor type identification without manual configuration

Performance Parameters

  • Temperature Measurement Accuracy: ±0.08 °C full scale
  • Channel Isolation Voltage: 1500 VAC channel to backplane bus
  • ADC Conversion Cycle Time: 0.9 ms per channel
  • Surge Withstand Capacity: 2 kV ESD contact discharge, 4 kV EFT
  • Vibration Resistance: 10–150 Hz, 1 g continuous operation
  • Max RTD Cable Length: 150 m shielded three-wire cable

Material Composition

  • PCB Substrate: FR4 high-Tg low-drift industrial fiberglass circuit board
  • Signal Terminals: Gold-plated phosphor bronze anti-corrosion terminal blocks
  • Reference Resistance: Ultra-low temperature drift precision metal film resistors
  • Shield Frame: Single-layer cold-rolled steel signal isolation shielding
  • Mounting Housing: Black extruded aluminum alloy hard anodized anti-corrosion coating

Structural Characteristics

  • Standard 1U dual-latch plug-in rack card structure
  • Front panel 8-group independent LED fault indicator array corresponding to each RTD channel
  • Rear gold finger connector docking with rack backplane bus
  • Independent wiring terminal compartment for three-wire RTD sensor cable access
  • Double isolation barrier between RTD analog circuit and digital bus circuit

Working Principle

Three-wire RTD resistance signals enter isolated signal conditioning circuits; internal precision reference resistors automatically compensate cable wire resistance error. Resistance value converts to digital temperature data via 16-bit ADC chips, linear correction executed according to stored RTD characteristic curves, temperature data transmits to rack main controller via ACN backplane bus. Hardware circuits continuously detect open-circuit and short-circuit faults of RTD sensor cables and trigger corresponding front panel alarm LED signals.

Advantage Highlights

  1. Automatic three-wire cable resistance compensation eliminates wiring length measurement error
  2. Auto-recognition of PT100/PT1000 sensors reduces on-site configuration workload
  3. Ultra-low drift precision reference resistors guarantee long-term stable temperature measurement
  4. Per-channel independent fault diagnosis quickly locates damaged RTD sensors
  5. Hot-swap maintenance without full rack power shutdown
  6. Factory pre-calibrated RTD characteristic curves without on-site calibration

Applicable Industries

  • Pulp mill process water, slurry medium temperature monitoring
  • Chemical reactor low-medium temperature closed-loop control
  • Municipal wastewater treatment pool temperature collection
  • Mining thickener overflow slurry temperature monitoring
  • Food & pharmaceutical production line constant temperature workshop monitoring

Installation Requirements

  1. Install inside standard Metso ACN CS 8/16-slot control rack
  2. Maintain 10 mm vertical ventilation gap between adjacent modules
  3. RTD field wiring uses dedicated three-wire shielded platinum resistance cable
  4. Cabinet PE grounding resistance ≤ 4 Ω to suppress external signal interference
  5. Stabilize rack backplane 24 VDC power before hot-swapping modules
  6. Control cabinet internal continuous operating temperature below 55 °C

Operation & Maintenance Precautions

  1. ESD anti-static wrist strap mandatory during module disassembly and wiring
  2. Avoid mixing RTD cables with power cables inside cabinet wiring channels
  3. Conduct semi-annual inspection of terminal block screw tightness
  4. Do not install adjacent to high-power frequency converter modules
  5. Spare modules stored in sealed anti-static packaging with desiccant packs
  6. Cut off field RTD sensor wiring terminals before disassembling terminal blocks

Reviews

There are no reviews yet.

Be the first to review “Metso D201472”

Your email address will not be published. Required fields are marked *

View Related Products