Product Short Description
Basic Identification
- Manufacturer: Honeywell
- Full Model Code: FC-PSU-UNI2450U V2
- Product Name: Universal High-Efficiency 24VDC 5A Safety Power Supply Module Revision 2
- Product Series: Honeywell Experion PKS & Safety Manager FC-Series Redundant Power Module Line
- Hardware Revision: V2 (Enhanced upgraded circuit architecture, cross-revision parallel compatible)
Description
Product Overview
Second-generation upgraded universal AC-DC redundant power supply module, direct form-fit functional replacement for V1.0 hardware. Incorporates upgraded thermal management, expanded fault diagnostic coverage, extended temperature operating range, and cross-revision parallel load-sharing compatibility with V1.0 units for staged cabinet system upgrades. Delivers stabilized 24 VDC power to all FC-series SIS/DCS hardware.
Technical & Performance Parameters
- AC Input Voltage Range: 85 VAC ~ 264 VAC universal global mains, 47–63 Hz
- DC Output Rating: 24 VDC ± 0.08% load regulation, 5 A continuous maximum output current
- Output Ripple Noise: < 8 mV peak-to-peak (improved from V1.0 10 mV)
- Full Load Energy Efficiency: 96.5% peak efficiency
- Power Factor Correction: ≥ 0.96 active PFC
- Standby Power Consumption: < 0.8 W no-load standby draw
- Galvanic Isolation Rating: 3500 VAC input-to-output isolation (upgraded from V1.0 3000 VAC)
- Integrated Protection Circuits: OVP, OCP, short-circuit auto-restart, multi-stage thermal shutdown, reverse polarity, surge voltage suppression
- Operating Temperature Range: -40 °C ~ +70 °C (expanded from V1.0 -10 °C ~ +50 °C)
- Storage Temperature: -45 °C ~ +85 °C
- Environmental Protection: IP54 double-layer silicone conformal PCB coating
- Physical Dimensions: Identical to V1.0: 120 mm × 85 mm × 51 mm
- Net Weight: 1.22 kg
- Certifications: CE, UL 508, FCC Class B, ATEX Zone 2, IEC 61508 SIL 3 Full Safety Certification
Material Composition
- Enclosure: Die-cast aluminum alloy with extended integrated cooling fin array (V2 upgrade)
- Power PCB: 6-layer FR4 high-current board with dual-layer silicone conformal coating
- Power Switching Semiconductors: Low Rds(on) silicon carbide MOSFETs for improved thermal efficiency
- EMI Filter: Three-stage toroidal inductor filter with enhanced surge suppression capacitors
- Digital Diagnostic Controller: Upgraded 32-bit industrial microcontroller for expanded fault monitoring
Structural Characteristics
- Identical compact half-width 19-inch rackmount form factor as V1.0 for drop-in replacement without cabinet modification
- Expanded front panel LED diagnostic indicators: Input Under-Voltage, Input Over-Voltage, Output Over-Current, Internal Heat Sink Over-Temp, Bus Communication Fault, Module Healthy
- Upgraded load-sharing control IC supports parallel pairing with V1.0 or V2 modules without voltage imbalance
- Sealed IP54 enclosure with improved dust/moisture ingress resistance for unconditioned industrial cabinet environments
- Backplane communication connector pinout fully backward compatible with V1.0 chassis IOBUS interfaces
Working Principle
- AC mains input passes through three-stage EMI surge filter and upgraded active power factor correction circuit
- Silicon carbide soft-switching converter generates ultra-low-ripple regulated 24 VDC isolated output with reduced heat generation
- 32-bit microcontroller samples 12 independent power supply operating parameters at 10 ms scan intervals
- Cross-revision compatible load-sharing logic dynamically balances output current between mixed V1.0/V2 parallel module pairs
- Granular fault diagnostic data transmitted via chassis backplane bus with individual fault code logging to Experion PKS central historian
Core Function Features
- Cross-revision parallel compatibility enables staged cabinet upgrades without full power supply replacement
- Expanded -40 °C low-temperature operating range supports outdoor unheated control cabinet deployment
- Enhanced 3500 VAC isolation rating improves protection against plant mains transient voltage surges
- Double-layer conformal PCB coating extends service life in high-humidity, salt-air offshore environments
- Granular fault code diagnostic reporting simplifies remote troubleshooting via central DCS HMI
Advantage Highlights
- Improved silicon carbide power semiconductors reduce cabinet heat load by 12% vs V1.0 hardware
- Wider operating temperature range eliminates need for cabinet heating/cooling systems in remote plant locations
- Backward mechanical and electrical compatibility reduces spare parts inventory costs for mixed V1.0/V2 systems
- Higher surge suppression circuit withstands industrial grid lightning transient voltage events without module shutdown
- SIL 3 certified with expanded fault coverage to reduce spurious safety system power feed trips
Applicable Industries
Offshore oil & gas SIS cabinets, remote pipeline ESD control, cold-climate refinery facilities, LNG storage terminal safety systems, mining underground process control racks
Installation Requirements
- Compatible for parallel redundant installation with FC-PSU-UNI2450U V1.0 modules in paired rack positions
- Independent AC mains circuit breakers mandatory for each parallel power supply unit
- Minimum 20 mm horizontal airflow clearance between adjacent power modules
- DC output wiring minimum 4 mm² copper cable connected to FC-IOCHAS dual redundant power bus terminals
- Backplane IOBUS communication wiring required to transmit full diagnostic fault codes to central safety processors
Usage Precautions
- Mixed V1.0/V2 parallel pairs must be configured via Experion PKS engineering workstation to enable cross-revision load-sharing algorithm
- V2 module maximum continuous output current derated to 4.5 A when paired with V1.0 hardware to match V1.0 thermal limits
- Double-layer conformal coating prohibits on-site PCB repair; module replacement required upon internal circuit failure
- Avoid enclosure ventilation fin blockage at all operating temperatures to prevent thermal shutdown
- Spare V2 modules may be installed as direct drop-in replacement for failed V1.0 units without cabinet wiring modification