Product Short Description
Product Name: Reliance Electric AVS-1700-ACX – Adjustable Speed Drive (ASD), 100 HP, 480 V AC, 3-Phase Input/Output
Product Overview:
The Reliance AVS-1700-ACX is a variable frequency drive (VFD) from the AVS-1700 series. Rated at 100 HP (75 kW), 480 V AC, 3-phase. Used for motor speed control in industrial applications.
Description
Technical Specifications:
| Parameter | Value |
|---|---|
| Power Rating | 100 HP (75 kW) |
| Input Voltage | 380–480 V AC, 3-phase, 50/60 Hz |
| Output Voltage | 0–480 V AC, 3-phase |
| Output Current | 110 A (rated) |
| Frequency Range | 0.5–400 Hz |
| Control Mode | V/F, Sensorless Vector, Closed-loop Vector (with encoder) |
| Overload Capacity | 150% for 60 seconds, 200% for 3 seconds |
| Braking | Dynamic braking (built-in chopper) |
| Communication | Modbus RTU (RS-485), DeviceNet, Ethernet/IP (option) |
| Enclosure Rating | IP20 (indoor) / IP54 (with enclosure) |
| Operating Temperature | -10°C to +50°C (derate above 40°C) |
| Dimensions (H×W×D) | 550 × 350 × 250 mm |
| Weight | 75 kg (165 lb) |
| Standards | UL 508C, CE, CSA C22.2 |
Functional Features:
- 7 programmable digital inputs
- 3 programmable analog inputs (0–10 V, 4–20 mA)
- 2 programmable relay outputs
- 1 programmable analog output (0–10 V, 4–20 mA)
- Built-in PID controller
- Energy-saving mode (auto V/F optimization)
- Motor thermal protection (PTC/KTY input)
- Auto-tuning for sensorless vector control
Material Composition:
- Enclosure: Galvanized steel, powder-coated (RAL 7035)
- Heat sink: Extruded aluminum (6063-T5)
- Power module: IGBT (650 V, 150 A) – Fuji/Mitsubishi
- PCB: FR-4, conformal coated, 2-layer + 4-layer power board
- Fan: Ball bearing, IP55 rated
- Terminal block: Phoenix Contact, UL listed
Structural Features:
- Front-accessible terminal block (no-tool wiring)
- LED status indicators: Power, Run, Fault, Alarm
- Keypad: LCD display with navigation buttons (or remote via PC)
- Removable fan module for maintenance
- DIN rail mounting option (for smaller frames)
Working Principle:
AC input → diode bridge rectifier → DC bus (capacitors) → IGBT inverter (PWM) → 3-phase AC output to motor. V/F ratio controls motor speed. In vector mode, drive estimates motor flux/torque for precise speed control.
Advantages:
- 100 HP in compact footprint
- Sensorless vector for pump/fan applications without encoder
- Built-in dynamic braking eliminates external resistor
- Multiple communication protocols for BMS integration
Applicable Industries:
- Pumping stations (water/wastewater)
- HVAC (chillers, cooling towers)
- Conveyor systems
- Compressors
- Mining and metals
Installation Requirements:
- Mount on vertical surface with adequate clearance (min 200 mm above, 100 mm below)
- Input cable: 4-core, 70 mm² Cu (for 100 HP)
- Output cable: 4-core, 70 mm² Cu, shielded (max 50 m)
- Ground cable: same size as power cable
- Torque terminals: 12 N·m (power), 2.5 N·m (control)
Usage Notes:
- Always install input reactor (5% impedance) for drives above 50 HP
- Do not operate motor above base frequency (60 Hz) without flux weakening
- Set motor nameplate data (voltage, current, FLA, RPM) before first start
- Derate output current 1% per °C above 40°C ambient