Product Short Description
Product Name: Honeywell CC-PAIH02
Product Introduction: A 8-channel, 0–10 VDC / 1–5 VDC analog input module for Honeywell Experion PKS and PlantScape DCS systems, designed for acquiring voltage signals from field transmitters (positioners, analyzers, custom sensors).
Model Series: Experion PKS I/O Series (CC-PAIHxx)
Description
Technical Specifications:
- Channels: 8 single-ended analog inputs
- Input Signal: 0–10 VDC or 1–5 VDC (user-selectable per channel)
- Input Impedance: 1 MΩ (high impedance, minimal loading)
- Resolution: 16-bit A/D converter
- Accuracy: ±0.05% of span (typical)
- Isolation: 500 VDC channel-to-channel, channel-to-bus
- Power Supply: 24 VDC (bus-powered from controller backplane)
Functional Features:
- Per-channel range selection: 0–10 V or 1–5 V via software configuration
- Diagnostics: Per-channel overrange, underrange, wire break detection
- Filter setting: Configurable digital filter (10 ms to 10 s) per channel
- Cold junction compensation: Not applicable (voltage input, not thermocouple)
Performance Parameters:
- Sampling rate: 100 ms per channel (all channels)
- Common mode rejection: 100 dB at 50/60 Hz
- Operating temperature: 0°C to +60°C
- Dimensions: 25 mm × 120 mm × 160 mm (half-width I/O module)
- Weight: 180 g
Material Composition: FR-4 multi-layer PCB, gold-plated backplane connector, metal film resistors, conformal-coated components
Structural Features: Half-width module for Experion PKS I/O carrier; 8 screw terminals on front for field wiring; LED indicators per channel (Power, Fault, Signal); backplane connector for carrier bus
Working Principle: The voltage signal from the field device is fed directly to the 16-bit A/D converter input (high impedance, 1 MΩ). The A/D converts the analog voltage to a digital value and transmits it to the Experion PKS controller via the backplane. The per-channel digital filter averages samples to reduce noise.
Advantages:
- High input impedance (1 MΩ) does not load field devices
- Flexible per-channel range selection (0–10 V or 1–5 V)
- 8 channels per module, compatible with existing Experion PKS I/O carriers
Applicable Industries: Valve position feedback, gas analyzers, custom process sensors, laboratory instruments, building automation (when integrated with Experion)
Installation Requirements:
- Insert into Experion PKS I/O carrier; set module address via DIP switches or software
- Use shielded twisted-pair cable for voltage signals
- Ensure signal source impedance is less than 10 kΩ for accurate readings
Usage Notes:
- Select correct input range (0–10 V or 1–5 V) per channel in configuration software before commissioning
- For long cable runs (>30 m), use 4–20 mA input module (CC-PAIH01) instead to avoid voltage drop errors
- Calibrate each channel via Experion PKS Configuration Studio