Product Short Description
Product Brief: Isolated relay output module for Ovation DCS, uses mechanical relay contacts to output switch signals, controls high-power field equipment and realizes logic interlock and on-off control.
Technical Specifications:
- Output Channel Quantity: 16 relay output channels
Description
- Relay Contact Type: Normally open (NO) contact
- Contact Rated Load: 250 VAC / 5 A (resistive load)
- Maximum Switching Voltage: 300 VAC
- Operating Temperature Range: 0 °C to +60 °C
- Storage Temperature Range: -40 °C to +85 °C
- Relative Humidity: 5% ~ 95% non-condensing
Functional Features:
- Each channel relay electrical isolation
- LED indication for each output channel status
- Built-in freewheeling diode for inductive load
- Relay coil surge suppression
- Hot-swappable design
- Output state feedback diagnosis
Performance Parameters:
- Relay Action Time: ≤ 8 ms
- Relay Mechanical Life: 12,000,000 operations
- Isolation Voltage: 1500 VAC coil to contact
- Contact On-resistance: ≤ 50 mΩ
- Bus Communication Rate: 1 Mbps
Material Composition:
- Casing: Flame-retardant industrial ABS
- PCB: FR-4 high-strength circuit board
- Relay: Industrial grade power relay with silver alloy contacts
- Internal Insulation Parts: High-temperature resistant engineering plastic
Structural Characteristics:
- 3U standard rack-mount size
- Front panel dense LED indicator area
- Rear backplane bus connector
- Independent partition for each relay to avoid mutual interference
Working Principle:
The DCS controller sends on/off control commands to the module via backplane bus. The internal drive circuit energizes or de-energizes relay coils to control the closing and opening of relay contacts. The contacts directly control the power loop of field motors, solenoid valves and contactors to complete switch control.
Advantages & Highlights:
- Mechanical contact isolation realizes strong and weak current complete isolation
- Large contact load capacity drives high-power field equipment directly
- Long mechanical service life for frequent switching loops
- Built-in surge protection adapts to inductive load working condition
Applicable Industries: Power plant auxiliary equipment control, chemical valve interlock, metallurgical motor control, industrial fan and pump control
Model Series: Emerson Ovation Relay Output Module Series
Installation Requirements:
- Install on DCS standard rack vertically
- Strong current output wiring uses thick wire in accordance with load current
- Inductive load must connect absorption components in parallel
- Keep ventilation to reduce relay operating temperature
Usage Notes:
- Never exceed contact rated voltage and current load
- Check contact ablation regularly under frequent switching
- Cut off external strong current power before module replacement
- Avoid long-term overload of relay contacts